HEF-H Simulator Transformer Test Equipment

HEF-H Simulator Transformer Test Equipment

Classification: Measurement Product/Secondary Circuit Test

Reference standard: JJG313-94,JJG314-94

Verification:  View the certificate

Instructions:  DOC Instructions

  PDF Instructions

Tel: 027-87207771 87207772 87207773 87188862

Verification certificate
Product introduction

HEF-H Simulator Transformer Test Equipment specilized for testing PT, CT error and the impedance, admittance test. Meet national JJG313-94 "Measuring Current Transformer test procedures" and JJG314-94 "Measuring voltage transformer test procedures" requirements.

Alternative name
Transformer calibrator, transformer test equipment
The Characteristics of the products

1, Uses 320 × 240 dot matrix LCD, visible range, with a long-life backlight, easy to use
2, the entire Chinese operation interface, attractive interface
3, the dial indicator, ratio difference, angle difference using large font display, user observation
4, the company's simulation-type transformer field calibrator fully meet JJG314-1993 and JJG314-1994 requirements, automatic sampling
5, automatically determine the polarity of the error, the error ratio
6, PC software with virtual instruments open function7, S-Class solve measurement problems
8, automatic switching range
9, using unique circuitry and advanced DSP technology combine to completely remove the RC phase shifter circuit instability
10, power consumption: <15VA (without micro-printer)         <25VA (with micro-printer)
11, harmonic rejection ratio:> 40db
12, Dimensions (L × W × H): 260 × 350 × 150mm3
13, Weight: 6kg

The parameters of the products

1 , Working environment
  1 ) Temperature : 5 ℃ ~ 40 ℃; Relative humidity : <80% (25 ℃ when )
    Altitude : <2500m
    Power frequency : 50Hz ± 0.5Hz; Supply voltage : 220V ± 5V
 2 ) Measuring range:
    Phase component ( % ) : 0.0001 ~ 200.0 ; Resolution : 0.0001
    Quadrature component ( stars ) : 0.001 ~ 700.0 ; resolution: 0.001
    Impedance (Ω): 0.0001 ~ 20.0; Resolution : 0.0001
    Admittance (ms): 0.0001 ~ 20.0; resolution: 0.0001
 3 ) Basic error:
    Phase component : ΔX = ± (X × 2% + Y × 2%) ± Dx ( with an optional )
    Orthogonal components : ΔY = ± (X × 2% + Y × 2%) ± Dy ( with an optional )
              "X", "Y" - the instrument display
              "Dx, Dy" - the quantization error of the instrument
               Dx = 2, Dy = 5
  4 ) dial indicator : level 2 ( level 1 available )
2, Scope of work:
 1 ) Current : (1% ~ 149%) In (In = 5A)
          (5% ~ 149%) In (In = 1A)
  2 ) Voltage : (5% ~ 149%) Un (Un = 100V, 150V, 100V /)
          (5% ~ 149%) Un (Un = 100V / 3)
3, the working load:
  1 ) Current : TO right TX <0.12Ω cosΦ = 1
  2 ) Voltage : a pair of x <0.25VA (100V)
4 , wrong polarity indication
  When the operating current ( voltage ) reaches the rated current ( voltage ) of more than 5% error for more than 180 %, the proper polarity indication .
  Note: If greater than the rated operating current ( voltage ) more than 10% , should not appear polarity indication , there is a fault , please do not increase the current
  ( Voltage ) , so as not to burn the instrument .
5 , ratio error indication :
  When the operating current ( voltage ) reaches the rated current ( voltage ) of more than 5% error of more than 30% but less than 180% , the proper ratio error indication.
6 , insulation and pressure test and description:
  Terminal TX () terminals connected
  Power outlet on the casing can withstand 1.5kV, 1min pressure


Power supply: AC110V/115V/120V/127V/220V/230V/240V optional
Input frequency: 50Hz/60Hz optional
Note: The users can select the corresponding power which based on their local supply voltage and frequency, and we will confirm it before the delivery (or inform us that the goods will be used in which country advance)